What Drainage Gradient Do I Need?
Quick Answer
100/110mm foul with WC: 1:80 min (1:40 without). Surface water: 1:100 min
Per Building Regulations Approved Document H. 1:40 = 25mm fall per metre
Minimum Gradients by Pipe Type
- 100/110mm foul drain (≥1 WC connected): 1:80 minimum (12.5mm per metre) per AD H Diagram 5 — WC flush provides self-cleansing velocity
- 100/110mm foul drain (no WC, low flow only): 1:40 minimum (25mm per metre)
- 150mm foul drain: 1:150 minimum
- 100mm surface water: 1:100 minimum (10mm per metre)
- 160mm surface water: 1:100 minimum
Understanding Gradient Notation
A gradient of 1:40 means the pipe falls 1 unit for every 40 units of horizontal run. In practical terms:
- 1:40 = 25mm fall per metre
- 1:60 = 16.7mm fall per metre
- 1:80 = 12.5mm fall per metre
- 1:100 = 10mm fall per metre
Why Gradient Matters
Too steep (steeper than 1:40) and the water runs ahead of the solids, leaving them behind to cause blockages. Too shallow and the flow velocity is insufficient to carry solids. The gradient creates a self-cleansing velocity of at least 0.75m/s.
Practical Example
For a 10m drain run from a house to a manhole at 1:40:
- Total fall: 10 × 25mm = 250mm
- If invert at house is 500mm deep, invert at manhole = 750mm deep
Building Regulations
Approved Document H sets out the requirements for below-ground drainage. All new drainage installations require Building Control notification. The gradient can be checked using Maguire’s Rule or the tables in Approved Document H.
Related Questions
Last updated: April 2026